MODEL C24EA - CONTROL BOARD
F35453 (July 2008) Page 38 of 68
DELIMING CYCLE STATUS
(LED INDICATORS)
Conditions same as listed under STARTING CONDITIONS.
Delime time delay relay 2 (TDR) and drain time delay relay (TDR) jumpers on the control board are set at their
default times as shown on the schematic.
Delime valve closed.
Delime solution added to steam generator.
NOTE: Heat exchanger elements are not energized during delime cycle.
Delime Switch On
Delime switch pressed to DELIME position (momentary on - hold 2 sec).
Power light (3LT) (amber) on.
Delime light (4LT) (red) on.
HL Led is on. Water level control powered.
Water fills steam generator at fast fill rate.
LED
STATUS
COMPONENT DESCRIPTION
ON OFF
1 X Same as starting conditions
12 X Same as starting conditions
13 X Power to delime 1 (TDR)
Relay timed out, no output to delime circuit. LED
remains lit as in Turning Steamer Off.
14 X Delime Relay (K4) energized. Delime 2 (TDR) powered thru K4-6/4 closed contacts
(N.O.). 120VAC output from delime 2 (TDR) load
terminal for 60 minutes.
Power to heating circuit, power light (3LT) and WLC
thru K4-5/3 closed contacts (N.O.).
15 X Delime Relay (K2) energized. K2-6/4 contacts close (powers delime light)
K2-5/1 contacts open. Power to cooking
compartment controls is locked out (no power to
timers or lights).
Power to delime 1 (TDR) input trigger and delime 1
(TDR) is energized. 120VAC output from load
terminal remains on for 3 additional minutes after
power is removed from input trigger to allow heat
exchanger to drain (delime valve energized). Total
time 63 minutes unless canceled (delime 2 TDR
default time of 60 minutes plus delime 1 TDR of 3
minutes).
Delime transformer (3T) powered. Delime valve
energized and opens.
Delime valve end switch contacts close.
17 X Delime Relay (K7) energized. K7 powered from delime 1 (TDR) output from load
terminal.
K7-5/1 N.C contacts open. X1 potential removed
from power switch (1S).
K7-5/3 N.O. contacts close. Allows delime 1 (TDR) to
remain powered to hold K7 energized for a delay on
drop out (120VAC output from load terminal remains
on) after K4-6/2 N.C. contacts open.
All other LED's are off.